Tank Farm & Inventory

High and high-high tank level alarms: overfill protection under API 2350

A high alarm warns that a tank is nearing its normal fill limit; the high-high alarm is the last layer before the critical level and should come from a sensor independent of the ATG.

Topic
Tank Farm & Inventory
Updated
13 November 2026
Reading time
6 min
Sections
7
The top rim of a large white storage tank with a platform and ladder.
Overview

A high alarm tells the operator that a tank is approaching its normal fill limit, while the high-high alarm is the final layer before the critical level and should come from a sensor separate from the ATG, as API 2350 recommends.

The automatic tank gauge (ATG) already raises level alarms, but the gauge can fail silently, and its alarms fail with it. API Standard 2350, Overfill Prevention for Storage Tanks in Petroleum Facilities, now in its 5th edition (2020), treats overfill prevention as a system of levels, people, procedures and independent equipment. This guide explains the alarm levels, the tank categories, how to set the high-high point and how to test it.

High, high-high and critical high: the levels

Levels of concern

High, high-high and critical high: the levels

Every tank has a height above which something bad happens: product spills over or the roof and shell are damaged. Everything else is set downward from that point.

API 2350 calls these heights levels of concern. Critical high is the highest level the product can reach without overflow or damage. High-high is the emergency alarm set far enough below critical high that the transfer can be stopped in time. The maximum working level is the highest level to which the tank is routinely filled. An optional AOPS level sits below critical high where an automated overfill prevention system is installed.

The ordinary high alarm, usually from the ATG, is an operational warning set by the site between the maximum working level and high-high. It tells the operator to prepare to stop, not that an emergency has begun.

Critical high (CH)
Overflow or damage above this level
AOPS level (optional)
Automatic termination, below CH
High-high (HH)
Emergency alarm with time left to stop
High (H)
Operational warning, usually from the ATG
Maximum working (MW)
Normal upper fill limit
Why high-high must be independent of the ATG

Independence

Why high-high must be independent of the ATG

If the same instrument both measures the level and raises the last alarm, a single fault can blind the operator at the worst moment.

Servo gauges can stick when a displacer catches on a still pipe. Radar gauges can lock onto a false echo from a nozzle or a heating coil. A gateway or power fault can freeze every value in the control room. In each case the ATG level stops rising on screen while the real level keeps rising, and an ATG-based high-high alarm never sounds.

Independence therefore means a separate sensor, and ideally separate wiring, power and alarm logic, so that one failure cannot take out both the measurement and the protection. Some radar gauges offer an independent second channel in one housing; Emerson describes this 2-in-1 function for the Rosemount 5900S as a back-up level and overfill prevention measurement. Whether it is independent enough for a given tank is a decision for the site's risk assessment.

Two layers of protection on one tank
Field
Control
Application
ATG

Measures level for inventory and raises the operational high alarm.

Hover, focus or tap a step to read its note.
API 2350 tank categories

Categories

API 2350 tank categories

API 2350 does not ask every tank for the same equipment. It sorts tanks into categories according to how the facility is attended, whether level is watched locally or remotely, and how alarms are handled.

The 5th edition added Category 0 for tanks gauged by hand only, and treats an automated overfill prevention system (AOPS) as an addition that can sit on top of the other categories. The table below gives the logic of each category in plain words.

One terminal can hold tanks of different categories, for example a tank that receives from ships at night and a tank filled only in daytime with staff on site. Use the standard itself for the exact criteria; API sells it through its webstore and the text should not be copied from unofficial sources.

CriterionHow level is watchedWhat it implies
Category 0Manual hand gauging onlyPeople and procedures carry all the protection
Category 1Personnel attend and watch level locallyLocal gauging and alarms during the whole receipt
Category 2Level sent to a control room by the ATGAlarms reach the operator remotely
Category 3Remote monitoring with less local attendanceIndependent high-high alarm in addition to the ATG
AOPS (additional)Automatic action without the operatorEngineered sensors, logic and valves
Setting the high-high point: response time decides

Setpoints

Setting the high-high point: response time decides

A high-high alarm is only useful if, after it sounds, there is still enough room in the tank for people to react. The setpoint is therefore calculated, not guessed, and the calculation is kept as an engineering document.

The calculation starts at critical high and works down. Take the maximum flow rate the tank can receive. Estimate the response time: how long it takes to detect the alarm, confirm it, and stop the pump or close the valve, including valve travel. Multiply rate by time to get a volume, and convert that volume to a height with the tank calibration table. The 5th edition of API 2350 puts more weight on these reaction times, and its annexes guide the calculation.

Write every setpoint, its basis and its date into a register. When a pump is upgraded and the fill rate goes up, the high-high point must move down. That link is easy to forget during a project that only touches the pumps, because the pump team rarely opens the tank alarm register.

  1. Fix critical high

    From tank construction: shell height, roof type, overflow points.

  2. Take the maximum fill rate

    From ship, pipeline or pump capacity, whichever is highest.

  3. Estimate response time

    Detect, confirm, stop pumps, close valves.

  4. Convert to height

    Rate times time gives volume; the tank table gives height.

  5. Place HH and MW

    HH below CH by that height; MW below HH with an operating margin.

  6. Record and review

    Keep a setpoint register and review it after any change in rate or tank.

Low and low-low alarms protect the pumps

The other end

Low and low-low alarms protect the pumps

Overfill gets the attention, but a tank pumped too low causes its own damage. Low and low-low alarms protect the equipment downstream of the tank.

When the level falls toward the suction nozzle, a pump starts drawing vapour and runs dry, which damages seals and bearings. On floating-roof tanks, pumping below the roof landing level puts the roof on its legs and creates a vapour space under it. A low alarm warns the operator to stop the transfer or switch tanks; a low-low alarm can trip the pump through an interlock, as the operating philosophy defines.

The low-low setpoint is set the same way as high-high, from the bottom up: the level at which damage begins, the outflow rate and the time needed to stop. Record it in the same setpoint register, and test it with the same discipline. In practice, low-low alarms are often skipped in periodic tests because they seem less dangerous than high-high.

Testing level alarms end to end

Testing

Testing level alarms end to end

An overfill alarm spends years doing nothing, which is exactly why it must be tested: a fault in a silent system stays hidden until the day it is needed.

A proper function test moves the real sensor, or simulates the process at the sensor, and checks every link: the signal, the logic, the horn and light at the tank farm, the alarm in the control room and the operator acknowledgement. Testing only the SCADA display proves nothing about the sensor on the roof.

The test interval comes from API 2350, the manufacturer and, where the function is a safety instrumented function, the IEC 61511 calculation; it should be written in the maintenance plan, not left to memory. Record each result on a test sheet, so auditors and the next crew can see the last known state of the alarm.

Alarm management matters too. ISA-18.2 sets out how to rationalise alarms so that high-high stands out instead of drowning in nuisance alarms. API 2350 itself does not require IEC 61511 for an AOPS, but many owners apply it when the overfill function trips valves automatically.

Tank and tag
Which sensor and setpoint were tested
Method
Real level, sensor actuation or simulation at the sensor
Links checked
Signal, logic, local horn and light, control room, acknowledgement
As found and as left
Setpoint and response before and after the test
Bypasses
Any inhibit applied and confirmation it was removed
Signatures
Technician and operations witness
Field notes from Citia level alarm work

In the field

Field notes from Citia level alarm work

On real sites, overfill protection succeeds or fails on details: sensor choice, documentation and testing during live operations.

In the high-low alarm project at Pertamina Lubuk Linggau (Aroja) in 2024, Citia installed a high-low alarm system on storage tanks using VEGAPULS 6X non-contact radar sensors. The control system warns at the high and low alarm limits; at high-high or low-low it can trigger an alarm or an interlock signal according to the operating philosophy. The aim was to prevent overfill, dry running of pumps and product loss.

Citia INTEGRA HLA follows the same structure: an ATG or independent level sensor, PLC or SCADA, and a local annunciator, with setpoints and alarm responses set in an engineering review.

Two other projects show the testing side. In the pump emergency shutdown project at Pulau Baai in 2025, wiring diagrams and cause and effect charts did not match the field. The team verified point to point, simulated the logic offline and cut over during a scheduled shutdown. The Cikampek tank-monitoring upgrade in 2025 ran loop checks and functional tests of alarms and interlocks before handover. Citia's notes on level alarm reliability add the maintenance point: sensors drift without regular calibration.

Terms used in this guide

Overfill
Product rising above the critical high level, causing spillage or tank damage.
Level of concern (LOC)
A defined tank level used to set alarms and actions under API 2350.
Critical high (CH)
Highest level product can reach without overflow or damage.
High-high (HH)
Emergency alarm level set below CH with enough time to stop the transfer.
Maximum working level (MW)
Highest level for routine filling.
AOPS
Automated overfill prevention system: sensors, logic and valves that stop a receipt without the operator.
Level switch
Point sensor that changes state when the liquid reaches its position.
Proof test
Periodic test that shows a protective function still works from sensor to final action.

Frequently asked questions

What is the difference between a high and a high-high alarm?

A high alarm is an operational warning that the tank is nearing its normal fill limit, while a high-high alarm is the emergency alarm just before critical high. The high alarm asks the operator to prepare; the high-high alarm demands the transfer stop now.

Why must the overfill alarm be independent of the ATG?

The overfill alarm must be independent because a stuck or frozen ATG would also silence any alarm that depends on it. A separate sensor, ideally with separate wiring and logic, keeps the last layer working when the gauge fails.

How often should a level switch be tested?

A level switch should be tested at the interval set by API 2350, the manufacturer and, for safety instrumented functions, the IEC 61511 calculation. Write the interval into the maintenance plan and test end to end, not just the display.

What is AOPS?

AOPS is an automated overfill prevention system that stops a receipt without operator action, using its own sensors, logic and valves. Under API 2350 it is optional and sits on top of the tank category, with its activation level set below critical high.

What is API 2350?

API 2350 is the American Petroleum Institute standard for overfill prevention for storage tanks in petroleum facilities, currently in its 5th edition (2020). It covers levels of concern, tank categories, alarms, response times and the management system around them.

Can the ATG high alarm serve as the high-high alarm?

Not where independence is required, because a single ATG fault would remove both the measurement and the last alarm. The ATG high alarm remains useful as the operational warning below high-high.

Next step

Prepare the technical discussion for your facility.

Bring the equipment list, diagrams and symptoms you have. The Citia team helps map the next step.

Related products and solutions

Keep reading