UndatedFinished
Cirebon Power: annual AQMS maintenance
This work is an annual preventive maintenance program for all Ambient Air Quality Monitoring Systems (AQMS) owned by Cirebon Power.

- Year
- Not recorded
- Location
- Cirebon, Jawa Barat
- Status
- Finished
- Work types
- Instrumentation, Sensor
- Updated
1) Monthly preventive maintenance (12 visits)
Every month, a routine visit covers all AQMS devices:
Thermo Scientific 42i (NO/NO₂/NOx Analyzer)
Thermo Scientific 43i (SO₂ Analyzer)
Thermo Scientific 49i (O₃ Analyzer)
FH62C14 (PM10 Monitor)
Environics 6100 (Multi-Gas Calibrator)
Zero Air Generator
PM activities include:
Cleaning the outer casing
Visual inspection & internal cleaning
Capillary inspection
Fan filter cleaning
Sample particulate filter inspection
Lamp voltage check
Leak test
Pump check
2) Computer system & network checks
These include:
Workstation
Monitor & keyboard
Printer
UPS
Communication switch
Checks of the power supply, electrical disturbance, and data communication
3) Spare parts management
The document also lists the existing spare parts for each analyzer, including:
O-ring
Pump repair kit
UV lamp
Flow transducer
Pressure transducer
Filter element
This helps ensure critical components are available, which shortens MTTR (Mean Time to Repair).
4) Proposed implementation
The document sets out a monthly PM schedule (Month 1-12) with a detailed checklist for each instrument.
The aim is to keep all devices in optimal condition throughout the year.
The work in one sentence
This work is an annual preventive maintenance service for all of Cirebon Power's air quality monitoring systems, carried out every month to maintain accuracy, reliability, and environmental compliance.